Data Center
Information technologies such as big data, AI, and industrial Internet are changing with each passing day. In order to meet the needs of new business development, it is urgent to strengthen the construction of data centers and promote business development. The Sugon Data Center product line has a complete product line portfolio that can cover a wide range of application needs and provide users with a “one-stop” data center solution.
Container data center is a standard module for building data center and can complete the capacity expansion of data center in a short time. At the same time, it can be used as module alone. Establishment of a separate disaster recovery site besides the main data center of enterprise for military projects, government confidentiality engineering, energy survey or large outdoor work activities should be the fast, flexible and best solution for enterprise-class data center.
Container data center has the advantages of high-density, energy saving and environmental protection, low PUE value, modular rapid deployment, one-stop professional services, on-demand deployment and fast delivery. It is one of the representations of the fourth-generation data center.
The Sugon C9000-F container solutions is a kind of overall solution designed and developed based on fourth-generation data center by the Sugon company. It has double integration, intelligent, energy efficient features with annual designed average PUE (Beijing area) not higher than 1.2.
Traditional Data Center | Containerized Data Center | |
Refrigeration Efficiency | Hot and cold channels are difficult to separate, blowing in long distance | Fully closed, hot and cold channels are separated, blowing in short distance |
Server Installation Density | Low,3KW/Rack | High, more than 12kW / Rack |
Power Usage Effectiveness (PUE) | Higher (2-3) | Low (less than 1.3) |
Installation and Maintenance | Commissioning in long time, inconvenient | Installation is simple, plug-and-play (water, electricity, network) |
Expansibility | Difficult to extend when business dramatically expand | Modular expansion is very flexible |
Turn-over time of Construction | 1-2 years | 2 -3 months |
Total Cost of Ownership (TCO) | High | Lower |
Return on Investment (RIO) | Lower | High |
Sugon C9000-F adopts a 40-foot standard container as the cabinet, the outside dimensions are 12 meters long, 2.5 meters wide and 2.6 meters high. The container is divided into two cabins, the main one and auxiliary on the length direction within the container. The main device uses top mounted air conditioning in fluoride pump natural cooling way and modular UPS technology.
The main technical parameters of Sugon C9000-F container:
- Outline Dimensions: 12 meters long, 2.5 meters wide and 2.6 meters high
- Cabinet Quantity: 10
- Rack Power Density: 15kVA, 12kW
- Available U: 400U
- Distribution Capacity: total capacity of 210kVA
- Ciry Power Input Capacity: 60kVA, the input switch specification is three-phase 380V, 100A
- UPS Input Capacity: 150kVA, the input switch specifications is three-phase 380V, 250A
- Cooling Capacity: 120kW
- The Extreme Maximum Power Consumption in Summer: 24.6kW
- The Extreme Minimum Power Consumption in Winter: 8.1kW
- Summer Limit PUE: 1.41
- Winter Limit PUE: 1.14
- Annual Average PUE in Beijing : 1.2.